Model and Ranges:
D2T
Range:
- Range No. 0: 0-25Pa
- Range No. 1: 0-60Pa
- Range No. 2: 0-125Pa
- Range No. 3: 0-250Pa
- Range No. 4: 0-500Pa
- Range No. 5: 0-1000Pa
- Range No. 6: 0-2500Pa
- Range No. 7: 0-5000Pa
- Range No. 8: 0-10000Pa
Output:
- Output 1: 0~10V DC (3 wires)
- Output 2: 4~20mA (2 wires)
- Output 8: RS485/Modbus
IP level: IP65
Medium: Non-combustible, non-corrosive air, insensitive to moisture, dust
Work Environment: -20~70°C
Medium Temp: 0~60°C
Temp. Compensation: 0~50°C
Working Pressure: overload 10xFS, burst 15xFS/burst 20xFS(≤1kPa)/10xFS(≥1kPa)
Accuracy: ±1.0%FS (±2%FS@25Pa)
Long term stability: ±0.5%FS/Year
Thermal effect: <0.05%FS/°C (zero), <0.08%FS/°C (FS)
Response time: 0.5-30s
Weight: 320g
Approval: CE
Accessory: Standard accessories include 1002(5mm ID PVC tube 2m) and A-S0 (including 3 brackets and screws). Options are A-S1, A-S2 and A-S7-X. They can be used for surface, panel or flush mount and should be ordered separately. See details in Accessories.